Zforce ZRP Arresters (Riser Pole)

The type ZRP distribution class arresters provides surge protection to overhead systems for riser pole applications.

Features:

  • Zforce mold-on polymer housing for the ultimate seal against moisture ingress
  • High strength Fibreglass for high fault-withstand design
  • Integrated Ground Lead Disconnect for fast, reliable operation. Operates in less than 2 seconds at 1 amp and less than 2 cycles at 1,000 amps

Performance:

  • The ZRP designs are tested in accordance with the latest ANSI/IEEE standards for metal oxide arresters. (patent no. 5,923,518)
  • High Current - Short Duration 100kA
  • Low Current - Long Duration 250 amps
  • Nominal discharge class per IEC 10kA
  • Duty Cycle - 10kA
  • Line Discharge Class per IEC: Class 1
  • Minimum Energy Capability - 100% production tests: 2.7kJ/kV
  • Fault Withstand Capability: 20kA
  • REA Listed