- Home
- Utility Products
- Distribution & Transmission Insulators
- Gen 2 15kV-46KV Post - F-Neck
Gen 2 15kV-46KV Post - F-Neck
Polymer Line Post Insulators 15kV-46kV
This is the Gen 2 newly designed distribution line post insulator family, catering to the 15kV-46kV voltage classes.
Features:
- Standard F-Neck head
- Gen 1 seal uses Crimp Under pressure technology
- Extended life, specially formulated silicon housing minimises maintenance needs
- Versatile so can be installed in a variety of orientations
For special lugs or other imperial sizes please
contact us
to discuss your requirement.
Part Number | Line Voltage kV | ANSI Class |
Assembly Weight kg | Rubber Length mm | Section Length mm | Dry Arc mm | Leakage mm | STL kg/kN |
SCL kg/kN |
MDCL kg/kN |
|
---|---|---|---|---|---|---|---|---|---|---|---|
|
15 | 51-1F | 3.1 | 101 | 297 | 158 | 310 | 2,268 | 1,270 | 612 |
![]() |
|
25 | 51-2F | 3.4 | 151 | 347 | 209 | 465 | 2,268 | 1,270 | 612 |
![]() |
|
35 | 51-3F | 3.7 | 201 | 397 | 259 | 620 | 2,268 | 1,270 | 612 |
![]() |
|
46 | 51-4F | 4 | 252 | 447 | 322 | 798 | 2,268 | 1,270 | 612 |
![]() |
|
15 | - | 3.5 | 102 | 335 | 159 | 310 | 2,268 | 1,270 | 612 |
![]() |
|
25 | - | 3.8 | 152 | 385 | 211 | 465 | 2,268 | 1,270 | 612 |
![]() |
|
35 | - | 4.1 | 201 | 433 | 262 | 620 | 2,268 | 1,270 | 612 |
![]() |
|
46 | - | 4.4 | 252 | 485 | 315 | 798 | 2,268 | 1,270 | 612 |
![]() |
Loading...
Loading...
|