Flameproof Cable Glands - FGE SWA Series

Electrical Connections FGE SWA series armoured cable glands are designed for use in Zone 1 and Zone 2 areas. Manufactured from nickle plated brass they are designed for industrial applications. Glands are supplied complete with locknut. See below for gland sizing.

General Specification and Area Classification:

  1. Group -II, Category -2 (zone 1)gas group IIC, conform to IEC 60079-0:2011, EN60079-1:2007 & EN60079-7:2007
  2. Electrical apparatus for dust for Zone 21 & 22 as per EN 60079-31:2009
  3. Environental: IP67 as per IEC60529
  4. Certification No: ITS12ATEX17637X
  5. Equipment Marking: II 2 GD Ex d IIC Gb /Ex e IIC Gb -20°C < Ta < 100°C Ex tb IIC -20°C < Ta < 100°C Db IP67, ITS12ATEX17637XElectrical Connections FG series armoured cable glands are designed for use in Zone 1 and Zone 2 areas. Manufactured from nickle plated brass they are designed for industrial applications. Glands are supplied complete with locknut.